🔌Wire Size & Voltage Drop Calculator - Cable Sizing, Ampacity, AWG to mm²
A cable that is too thin causes two problems: too much voltage drop, leaving the load under-voltage, and overheating beyond what the insulation allows. This tool calculates voltage drop and losses from resistivity with temperature correction, applies a simplified ampacity reference with installation-method, ambient and grouping factors, and recommends the smallest size that satisfies both, with a breaker hint. It also covers 12 V / 24 V long runs, LED strip voltage and an AWG conversion table.
Free · No sign-up · Runs in your browserLast updated:
Loading tool...
How to use Wire Size & Voltage Drop Calculator
- 1Pick a preset or set the system (DC, single or three phase), voltage, current or power and one-way length
- 2Choose copper or aluminium, insulation, installation method, ambient temperature and number of bunched circuits
- 3Set the allowed drop (e.g. 3% lighting, 5% other) and read the recommended size, breaker, drop, voltage at the load and losses
- 4In Low-voltage runs compare 12, 24 and 48 V and see the voltage and brightness along an LED strip
FAQ
- How do you calculate voltage drop?
- In DC and single-phase circuits current flows out and back, so ΔU = 2 × I × L × R′ (for AC multiply by power factor and add the reactance term). Three-phase uses the line voltage: ΔU = √3 × I × L × (R′cosφ + X′sinφ). R′ = ρ/S, with copper at 0.0172 Ω·mm²/m at 20 °C; at 70 °C resistance is about 20% higher.
- What voltage drop is acceptable?
- A common reference from IEC 60364 is 3% for lighting and 5% for other uses when supplied from the public low-voltage network; the US NEC recommends about 3% for a branch circuit and 5% overall. Solar DC wiring is usually kept to 1–3%. Excess drop wastes energy, heats motors, dims LEDs and slows charging.
- If the ampacity is enough, why check voltage drop?
- Ampacity only keeps the cable from overheating and does not depend on length, while voltage drop grows with length. Short runs are usually sized by ampacity; long runs — a pump 100 m away, an EV charger across the yard, a 12 V solar array — are often sized by voltage drop. The tool computes both and tells you which governs.
- Why do 12 V systems need such thick wire?
- For the same power, current scales as 1/V and percentage drop as 1/V². A 120 W load draws 10 A at 12 V but only 0.5 A at 230 V, so on the same cable the 12 V percentage drop is about 370 times larger. That is why RVs and solar systems move to 24 V or 48 V and LED strips need power injected every 5 m or so.
- Can I use this ampacity table for an installation?
- Not directly. It summarises typical copper values from IEC 60364-5-52 / GB/T 16895.6 Annex B, with aluminium estimated by a factor, and real ratings depend on cable construction, soil resistivity, harmonics and fault protection. Follow your local code — NEC, BS 7671, AS/NZS 3008 or similar — and have a licensed electrician confirm.
Features
- DC, single-phase and three-phase drop formulas with conductor temperature and AC reactance
- Sizing by both voltage drop and derated ampacity, showing which governs, with an I_B ≤ I_n ≤ I_z breaker check
- Cable loss in watts, as a share of load power, and its yearly energy cost
- Drop-versus-length chart for neighbouring sizes so you see when to step up
- LED strip voltage profile for single- and double-ended feeds, with a 12 / 24 / 48 V comparison
- Two-way AWG ↔ mm² conversion table with diameter and resistance per km
Related tools
- 🌡️Thermal Expansion Calculator
- 🛰️Gravity Assist & Interplanetary Transfer Simulator
- ❄️Heat Pump & Air Conditioner Calculator
- 🧲Superconductivity Simulator
- 🛝Brachistochrone Race (Cycloid vs Line, Arc, Parabola)
- 🧭Earth’s Magnetic Field & Aurora (Dipole, Declination, Van Allen Belts)
- ⚛️Nuclear Fission Reactor Simulator
- 🦇Sonar, Radar & Echolocation